    The following form allows you to view linux man pages.

    Command:

    upscode2

    
    
    

    NOTE

           This man page only documents the hardware-specific features of the
           upscode2 driver. For information about the core driver, see
           nutupsdrv(8).
    
    
    

    SUPPORTED HARDWARE

           This driver supports UPS equipment which can be controlled via the
           UPScode II protocol. This is mainly Fiskars, Powerware equipment, but
           also some (probably OEM'ed) products from Compaq.
    
    
    

    EXTRA ARGUMENTS

           This driver supports the following optional settings in the
           ups.conf(5):
    
           manufacturer=value
               Autodetection of this parameter is not possible yet (and it
               probably never will be). Therefore, this user-defined string
               accepts any name. The default is unknown.
    
           input_timeout=value
               The timeout waiting for a response from the UPS. Some UPS models
               have shown to be rather slow, resulting in frequent messages about
               empty responses from the UPS. If you see this, try increasing this
               value.
    
           output_pace=value
               Delay between characters sent to the UPS. This was added for
               completeness with the above parameter. It has not shown to be
               needed yet.
    
           baudrate=value
               The default baudrate is 1200, which is the standard for the UPScode
               II protocol.
    
           full_update_timer=value
               Number of seconds between collection of normative values.
    
           use_crlf
               Flag to set if commands towards to UPS need to be terminated with
               CR-LF, and not just CR.
    
           use_pre_lf
               Flag to set if commands towards to UPS need to be introduced with
               an LF. A Compaq T1500h is known to need this.
    
    
    

    COMMANDS

           The driver supports the following commands for those UPSen that support
           them. The available commands are autodetected during initialization, so
           you should check availability with upscmd -l.
    
           ?   test.panel.start - Start UPS self test
    
               1 minute
    
    
    

    NOTES

           The Powerware UPS models that this driver has been tested against until
           now have not returned a value for battery.charge. Therefore, the driver
           will guestimate a value based on the nominal battery min/max and the
           current battery voltage.
    
    
    

    AUTHOR

           Havard Lygre <hklygre@online.no>, Niels Baggesen <niels@baggesen.net>
    
    
    

    SEE ALSO

       The core driver:
           nutupsdrv(8)
    