    Command:

    bcmxcp

    
    
    

    NOTE

           This man page only documents the hardware-specific features of the
           bcmxcp driver. For information about the core driver, see nutupsdrv(8).
    
    
    

    SUPPORTED HARDWARE

           This driver should recognize all serial BCM/XCP-compatible UPSes. It
           has been developed and tested on Powerware PW5115 and PW9120 hardware.
           If your UPS has a USB connection, you may also consult the
           bcmxcp_usb(8) driver documentation.
    
    
    

    EXTRA ARGUMENTS

           This driver supports the following optional settings in the
           ups.conf(5).
    
           shutdown_delay=delay
               The number of seconds that the UPS should wait between receiving
               the shutdown command (upsdrvctl shutdown) and actually shutting
               off.
    
           baud_rate=rate
               Communication speed for the UPS. If this is set to 9600, it tries
               to connect to the UPS at 9600bps. If it fails to communicate, it
               will go into baud-hunting. It starts at 1200 and goes up to 19200.
               If it succeeds, it tell you the speed it connected with. If not
               included in the config, it defaults to baud-hunting.
    
    
    

    DEFAULT VALUES FOR THE EXTRA ARGUMENTS

           ?    shutdown_delay = 120
    
           ?    baud_rate = none
    
    
    

    INSTANT COMMANDS

           This driver supports the following Instant Commands:
    
           shutdown.return
               Turn off the load and return when power is back.
    
           shutdown.stayoff
               Turn off the load and remain off.
    
           test.battery.start
               Start a battery test.
    
           outlet.n.shutdown.return
               Turn off the load on outlet n and return when power is back. (n is
               the outlet number reported by the upsc command)
    
    
    

    TODO LIST

           Report UPS statistics information
               BCM/XCP supports reporting of UPS statistics data.
    
           Change settings
    
       Internet resources:
           The NUT (Network UPS Tools) home page: http://www.networkupstools.org/
    
    
    

    Network UPS Tools 10/09/2011 BCMXCP(8)

    
    